Pollution Testing
Dim. of Climate Test Hall: Ø18 m. x 23 m. height
Dim. of Climate Test Chamber: 3 m. length x 3 m. width x 5 m. height
| Standard | Max. A.C. Volt | Max. D.C. Volt | Temp. from - to °C |
| Salt Fog | IEC 60507 | 900 kV | ± 1200 kV |
|
| Clean Fog | IEC 60507 | 900 kV | ± 1200 kV |
|
| Dry Salt Layer | See below
| 900 kV | ± 1200 kV |
|
| Environmental | IEC 60068 | 180 kV | ± 220 kV | -60°C to +70°C |
| Icing Tests | IEC 60694 | 900 kV | ± 1200 kV | 0°C to -15°C |
| Temp. rise test | AC | 4300 A 50 V |
|
|
|
| 2000 A 100 V |
|
|
|
| 4000 A 50 V |
|
|
|
| 1500 A 140 V |
|
|
|
| (3-phase) |
|
|
| DC |
| 2000 A 5 V |
|
|
|
| (on high potential up to 1200 kV) |
|
Other Tests Performed: DSL - Dry Salt Layer method: A method that simulates the deposit of air-borne contaminants with a negligible non-soluble component, typical of coastal conditions. The DSL is applicable to all types of insulators and apparatus and can be used for both a.c. and d.c. DCM - Dust Cycle Method: A pollution test method valid for all environments with a significant amount of non-soluble pollution deposit, e.g. desert and industrial environments. The DCM has the same test philosophy and applicability as the DSL.