High-Voltage TestingSTRI is in general accredited for performing tests in accordance with IEC 60060-1, edition 1989-11 for product standards according to the table below and for the following voltage types and levels:
- DC 10 kV up to 1200 kV
- AC 2 kV up to 1050 kV
- LI 50 kV up to 2600 kV
- SI 100 kV up to 1750 kV
- PD 1 pC up to 2 nC
- Cap 20 pF up to 1 ΅F
- Tan d 5x10-5 up to1 rad (0,005 up to 1%)
- RIV ~0 up to 5000 ΅V
- AC current 800 up to 6000A
- Resistance 10 up to 500 ΅ohm
- Temperature -40°C up to +125°C
Scope of accreditation:
| Standard | Edition | Title | Paragraph |
| IEC 60044-8 | Ed. 1, 2002-07 | Instrument transformers. Part 8: Electronic cur-rent transformers | 8.3.2-3, 9.2.2 |
| IEC 60060-1 | Ed. 3, 2010-09 | High-voltage test techniques Part 1: General def-initions and test requirements | Whole, except par 9 |
| IEC 60060-2 | Ed. 3, 2010-11 | High-voltage test techniques Part 2: Measuring Systems | Whole, except pollution testing with DC |
| IEC 60099-4 | Ed. 2.2, 2009-05 | Surge arresters Part 4: Metal-oxide surge ar-resters without gaps for a.c. systems | 8.2, 8.12, 10.8.12 |
| IEC 60137 | 2008-07 | Insulated bushings for alternating voltages above 1 000 V | 7.1, 8.1- 8.7, 9.1-9.5 |
| IEC 60168 | 2001-04 | Tests on indoor and outdoor post insulators of ceramic material or glass for systems with nomi-nal voltages greater than 1 000 V | 4.1-4.9 |
| IEC 60230 | Ed. 1, 1966 | Impulse tests on cables and their accessories | Whole |
| IEC 60270 | Ed. 3, 2000-12 | High voltage test techniques Partial dis-charge measurements | Whole, except 4.5.2-4.5.4 |
| IEC 60358-1 | Ed. 1.0, 2012-06 | Coupling capacitors and capacitor dividers | 9.2, 10.1-10.4 |
| IEC 60383-1 | 1993-04 | Insulators for overhead lines with a nominal voltage above 1 000 V Part 1: Ceramic or glass insulator units for a.c. systems Definitions, test methods and acceptance criteria | 13, 14, 15.1 |
| IEC 60383-2 | 1993-04 | Insulators for overhead lines with a nominal voltage above 1 000 V Part 2: Insulator strings and insulator sets for a.c. systems Definitions, tests methods and acceptance criteria | Whole |
| IEC 60437 | Ed. 2, 1997-09 | Radio interference test on high-voltage insulators | Whole |
| IEC 60502-2 | 2005-03 | Power cables with extruded insulation and their accessories for rated voltages from 1 kV up to 30 kV. Part 2: Cables for rated voltages from 6 kV up to 30 kV. | 16.3, 16.4, 18.1.3, 18.1.5, 18.1.7, 18.1.8, 18.2.3, 18.2.4 |
| IEC 60502-4 | Ed. 3, 2010-12 | Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um=1,2 kV) up to 30 kV (Um=36 kV) Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um=7,2 kV) up to 30 kV (Um=36 kV | AC dry and wet DC dry PD at ambient PD at Θt Imp. at ambient Imp. at Θt Heat. cycle in air Heat. cycle in water |
| IEC 60507 | 1991-04 | Artificial pollution tests on highvoltage insulators to be used on a.c. systems | Whole |
| IEC 60660 | 1999-10 | Insulators - Tests on indoor post insulators of or-ganic material for systems with nominal voltages greater than 1 000 V up to but not including 300 kV | 3.3-3.6, 5.4 |
| IEC 60700-1 | Ed. 1.0, 2008-08 | Amendment 2, Thyristor valves for high voltage direct current (HVDC) power transmission Part 1: Electrical testing. | 6-8, 9.3.1 (not temp), 10 |
| IEC 60840 | Ed. 4.0, 2011-11 | Power cables with extruded insulation and their accessories for rated voltages above 30 kV up to 150 kV - Test methods and requirements | 9.2-9.3, 10.12, 12.4.4-12.4.7, 13.2.4-13.2.5, 13.3.2.4, 14.4b-e, 15.4.2a-f, An-nex E, Annex G (not LI<50 kV) |
| IEC 60871-1 | Ed. 3, 2005-07 | Shunt capacitors for a.c. power systems having a rated voltage above 1 000 V. Part 1: General | 10, 16 |
| IEC 60885-2 | Ed. 2, 1987 | Electrical test methods for electric cables. Part 2: Partial discharge tests | Whole |
| IEC 60885-3 | Ed. 1, 1988 | Electrical test methods for electric cables. Part 3: Test methods for partial discharge measurements on lengths of extruded power cable | Whole |
| IEC 61109 | 2008-05 | Composite insulators for a.c. overhead lines with a nominal voltage greater than 1000 V - Defini-tions, test methods and acceptance criteria | 10.1, 11.1 |
| IEC 61245 | 1993-10 | Artificial pollution tests on high-voltage insula-tors to be used on d.c. systems | Whole |
| IEC 61284 | Ed. 2, 1997-09 | Overhead lines Requirements and tests for fittings | 14 |
| IEC 61442 | Ed. 2, 2005-03 | Test methods for accessories for power ca-bles with rated voltages from 6 kV (Um =7,2 kV) up to 30 kV (Um=36 kV) | 4.1-4.3, 5.2-5.3, 7.2, 20 |
| IEC 61462 | Ed. 1, 2007-02 | Composite hollow insulators Pressurized and unpressurized insulators for use in elec-trical equipment with rated voltages greater than 1 000 V Definitions, test methods, acceptance criteria and design recommendations | 7.2.2, 7.2.5.3, 7.4.2 |
| IEC 61813 | Ed. 1, 2000-10 | Live working Care, maintenance and in-service testing of aerial devices with insulating booms | 8.1.2, 8.1.5 |
| IEC 61869-1 | 2007-10 | Instrument transformers Part 1: General re-quirements | 7.2.3.2.1-2 |
| IEC 61869-2 | Ed. 1, 2012-09 | Instrument transformers Part 2: Additional requirements for current trans-formers | 7.2.2-7.2.3, 7.3.1, 7.4.3 |
| IEC 61869-3 | Ed. 1, 2011-07 | Instrument transformers Part 3: Additional requirements for inductive volt-age transformers | 7.2.2-7.2.3, 7.3.1-7.3.2, 7.4.3 |
| IEC 61869-5 | Ed. 1, 2011-07 | Instrument transformers Part 5: Additional requirements for capacitor volt-age transformers | 7.2.2-7.2.4, 7.2.501, 7.3.1, 7.3.501-7.3.504, 7.3.2, 7.4.1, 7.4.3 |
| IEC 61952 | Ed. 2, 2008-05 | Insulators for overhead lines Composite line post insulators for A.C. systems with a nominal voltage greater than 1 000 V Def-initions, test methods and acceptance criteria | 10.2.3, 11.1 |
| IEC 62067 | Ed. 2.0, 2011-11 | Power cables with extruded insulation and their accessories for rated voltages above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV) - Test methods and requirements | 9.2-9.4, 10.5, 10.10, 10.12, 10.13, 11.2, 12.4.4-12.4.7, 13.2.4-13.2.5, 13.3.2.4, Annex E, Annex G |
| IEC 62155 | 2003-05 | Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equip-ment with rated voltages greater than 1000 V | 10.4 |
| IEC 62199 | Ed. 1, 2004-05 | Bushings for d.c. application | 8.1-8.4, 9.1-9.6, 10, 10.2-10.3 |
| IEC 62217 | Ed. 2, 2012-09 | Polymeric HV insulators for indoor and outdoor use General definitions, test methods and acceptance criteria | 9.2.4, 9.2.7, 9.4.2 |
| IEC 62231 | Ed. 1, 2006-02 | Composite station post insulators for substations with a.c. voltages greater than 1000 V up to 245 kV - Definitions, test methods and acceptance criteria | 8.2.3, 8.2.6, 8.5, 9.2.1-9.2.2 |
| IEC 62271-1 | Ed. 1.0, 2011-06 | High-voltage switchgear and controlgear Part 1: Common specifications | 6.2.6.1-6.2.6.2, 6.2.7.1-6.2.7.3, 6.2.9, 6.2.11, 6.3, 6.4.1, 6.5, 6.9.1.1, 7.1, 7.3, 7.5 |
| IEC 62271-100 | 2008-04 | High-voltage switchgear and controlgear - Part 100: High-voltage alternating-current circuit-breakers | 6.1, 6.2.1-6.2.9, 6.2.11, 6.3, 6.5, 7.1 |
| IEC 62271-102 | 2001-12 | High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earth-ing switches | 6.1, 6.2.1-6.2.9, 6.2.11, 6.103, 6.104, 7.2 |
| IEC 62271-108 | Ed. 1, 2005-10 | High-voltage switchgear and controlgear Part 108: High-voltage alternating current disconnecting circuit-breakers for rated volt-ages of 72,5 kV and above | 6.2-6.3, 6.4.1, 6.5, 6.9.1.1, 6.102.9.4, 6.114.1, 7.1, 7.3 |
| IEC 62271-109 | Ed. 2, 2008-11 | High-voltage switchgear and controlgear Part 109: Alternating-current series capacitor by-pass switches | 6.2-6.3, 6.4.1, 6.5, 6.9.1.1, 6.101-6.102, 7.1, 7.3 |
| IEC 62271-200 | Ed. 2.0, 2011-10 | High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV | 6.2.6.1-6.2.6.2, 6.2.9, 6.2.11, 6.2.101, 6.4.1, 6.5, 6.9.1.1, 6.104, 7.1, 7.3, 7.5, 7.101 |
| IEC 62271-203 | Ed. 2.0, 2011-09 | High-voltage switchgear and controlgear - Part 203: Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | 6.2.6.1-6.2.6.2, 6.2.7.1-6.2.7.3, 6.2.9, 6.2.11, 6.3, 6.4.1, 6.5, 6.9.1.1, 7.1, 7.3, 7.5 |
| IEC 62501 | Ed. 1.0, 2009-06 | Voltage sourced converter (VSC) valves for high-voltage direct current (HVDC) power transmission Electrical testing | 4, 7, 9, 9.1, 9.2, 9.3, 9.3.1-9.3.4 |
| IEEE std. 4 | 1995 Amd. 4a, 2001 | IEEE Standard Test Techniques for High-Voltage Testing | Whole, except 6, 7, 8 and 9 |
| IEEE std. 482 | 2009 | Test Procedures and Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated Insu-lation Rated 2.5 kV through 765 kV or Ex-truded Insulation Rated 2.5 kV through 500 kV | See validation document |
| IEEE std. 822 | 2002 | Test Procedure for Impulse Voltage Tests on Insulated Conductors | Whole, except 3.2, 5.3-5.5 |
| IEEE std. 4042 | 2012 | Extruded and Laminated Dielectric Shielded Cable Joints Rated 2.5 kV to 500 kV | Whole, except 7.8.2 |
| IEEE C57.13.52 | 2009 | Performance and Test Requirements for In-strument Transformers of a Nominal System Voltage of 115 kV and Above | Whole, except 10.3-10.5, 12.1 |
| IEEE C57.19.002 | 2004 | IEEE Standard General requirements and Test Procedure for Power Apparatus Bush-ings | 7.3.1 |
| IEEE C63.4 | 2009 | Methods of Measurement of Radio-Noise Emissions from Low-Voltage Electrical and Electronic Equipment in the Range of 9 kHz to 40 GHz | Whole |
| CISPR 16-1-1 | Ed. 3.0 2010-01-01 | Specification for radio disturbance and im-munity measuring apparatus and methods Part 1-1: Radio disturbance and immunity measuring apparatus Measuring apparatus | Quasi-peak de-tector, band B |
| CISPR 18-2 | Ed. 2, 2010-06 | Radio interference characteristics of over-head power lines and high-voltage equip-ment. Part 2: Methods of measurement och procedure for determining limits | Quasi-peak de-tector, band B |
1This standard is replaced by IEC 62271-1, 2007-10.
2All IEEE-standards is based on IEEE std. 4, 1995 and Amd. 4a, 2001. This standard can be equally compared with the versions of IEC 60060 earlier than 2010. This means that impulse voltage tests cannot be performed according to any IEEE-standard.
In case of question please contact our Manager Quality Assurance